The Medical Center Company
Electrical Design Guidelines
a. An 11,400 volt nominal three phase, three wire, grounded wye system with ground fault current limiting resistors. Substations connected to this system are connected to two feeders by primary selector switches with momentary paralleling capabilities. Correct phase sequencing is essential for the normal operation of this system. Each feeder source to a service is energized at all times. It is normal, in this system, to have the load side of switches energized. USE CAUTION AT ALL TIMES.
b. Two 2400 volt, three phase, three wire delta systems;
Some substations connected to these systems are served with two cables in a primary selective configuration and some are connected with a simple radial feeder.
After careful consideration of proposed and existing electrical loads, Medical Center Company will assign a source or sources of power. Please provide preliminary electrical load and power factor information to Medical Center Company.
All equipment connected to the Medical Center Company system shall be rated for 500MVA fault withstand capability.
This document is C:\project\office\Design Guidelines & Procedures\Electrical Design guidelines.doc