The Medical Center Company
Electrical System Installation Requirements
1. Introduction
2. System Description
3. Approvals
4. Scheduling of Power Shutdowns and Power Transfers
5. Service Entrance
6. Feeder Systems
7. Service Equipment Rooms
8. Switchgear and Transformers
9. Metering
10. Manhole Construction
11. Duct Bank Systems
12. Testing
Revision History
|
Section |
Description |
Date |
|
- |
Original Issue |
7/15/97 |
|
Metering |
Added test switches and testing requirement |
9/4/97 |
|
Feeder Systems |
Deleted minimum feeder size |
3/23/98 |
The Medical Center Company power distribution system consists of the following:
a. An 11,400 volt nominal three phase, three wire, grounded wye system with ground fault current limiting resistors;
Substations connected to this system are connected to two feeders via primary selector switches with momentary paralleling capabilities. Correct phase sequencing is essential for the normal operation of this system. Each feeder source to a service is energized at all times. It is normal, in this system, to have the load side of switches energized. USE CAUTION AT ALL TIMES.
b. Two 2400 volt, three phase, three wire delta systems;
Some substations connected to these systems are fed with two cables in a primary selective configuration and some are connected with a simple radial feeder.
Notes on Primary Selective or Loop Type Distribution Systems:
The following is a typical installation procedure and is intended to indicate the steps necessary to safely commission a new feeder. These steps must be performed in coordination with Medical Center Company.
This document is C:\project\office\Design Guidelines & Procedures\Electrical installation requirements.doc